摘
厂房位吉林省长春市建筑总面积5090方米首层标准成建筑面积1200m2室效建筑面积220m2顶层建筑面积70m层高42m建筑室外高差4m
消火栓水系统采时高压消防水系统消防水水泵接合器室外蓄水池位建筑顶层高位水箱供首层标准层层设4消火栓顶层室设消火栓系统设4根竖根立流量104Ls消防水量208Ls消火栓立径DN100干径DN125
动喷水灭火系统采湿式动喷水灭火系统配水网端中式布置采垂式喷头长边33m行配水支短边32m垂直配水支长方形均匀布置层设喷头110四层总计440动喷水灭火持续时间1h喷淋水室外蓄水池高位水箱水泵接合器提供水箱位建筑物顶层容纳15m3贮水量
[关键词]消火栓 动喷水灭火系统 设计 民建筑设计防火规范
目录
1 原始资料···············································································1
11 图纸资料·············································································1
12 文字资料·············································································1
13 建筑参数·············································································1
14 设计规范·············································································1
2 消火栓水系统·······································································8
21 方案拟定·············································································8
22 消火栓水系统布置······························································9
23 材设备连接····································································10
24 消火栓水系统设计计算························································10
3 动喷水灭火系统···································································15
31 方案拟定·············································································15
32 动喷水灭火系统布置····························································16
33 材安装···········································································18
34 动喷水灭火系统设计计算···················································18
参考文献·····················································································24
1 原始资料
11 图纸资料
1建筑首层面图1:100(例建筑图)
2建筑标准层面图1:100
3室面图(消防水层)
4顶层面图1:100
12 文字资料
1建筑区长春市
2长春市冻土深度169 m
3城市水网径200 mm顶埋深1800 m
4城市供水压力50 Kpa
5电源城市提供路独立电源
13 建筑参数
1该建筑总面积5090方米
2四层厂房水箱间泵房组成
3首层建筑面积标准成建筑面积1200m2室效建筑面积220m2顶层建筑面积70m层高42m
4室外蓄水池深25m
5建筑室外高差4m
14 设计规范
1高低层建筑划分
般情况民建筑根建筑高度建筑层数分高层建筑底层建筑划分取决扑救火灾时消防设备登高工作高度消防车供水高度目前国参考国外部分高层建筑起始高度线确定国高层建筑起始高度线:建筑高度24m住宅建筑层高10层
2 水箱设置
(1) 底层建筑消防水箱应储存10min消防水量室消防水量超25Ls时计算水箱消防贮水量超12m3采12m3室消防水量超25Ls计算水箱消防贮水量超18m3采18m3
(2) 高层建筑消防水箱贮水量类建筑应18m3二类建筑类建筑住宅应12m3二类建筑住宅应6m3
(3)建筑高度超100m建筑水箱高度应保证建筑物利消火栓静水压力007MPa建筑高度超100时水箱高度应保证建筑物利消火栓静水压力015MPa高位水箱满足述求时应设增压设施
3底层建筑消防水量
建筑物设消火栓动喷水灭火设备时室消防水量应时开启时水量计算室消火栓水量应根时水枪数量充实水柱长度计算决定应表规定
表11 低层建筑室消火栓水量
建筑物名称
高度hm层数体积Vm3座位数n
消火栓水量(L·s1)
时水枪数量支
根竖流量(L·s1)
厂房
h≦24
V≤10000
V>10000
5
2
5
10
2
10
24
25
5
15
30
6
15
仓库
h≦24
V≤10000
V>10000
5
10
1
2
5
10
24
30
40
6
8
15
15
科研楼试验楼
H≤24V≤10000
10
15
2
3
10
10
H≤24V>10000
车站码头机场候车楼展览建筑等
5000
2
10
25000
3
10
V>50000
20
4
15
剧院电影院会堂礼堂体育馆等
800
2
10
1200
3
10
5000
4
15
N>10000
30
6
15
商店旅店等
5000
2
10
10000
3
10
V>25000
20
4
15
病房楼门诊楼等
5000
2
5
10000
2
10
V>25000
15
3
10
办公楼教学楼等民建筑
层数≥5层V>10000
15
3
10
国家级文物保护单位重点砖木木结构建筑
V≤10000
20
4
10
V>10000
25
5
15
住宅
层数≥8
5
2
5
4消火栓水系统相关计算公式
(1)水枪充实长度:
(11)
式中 SK:水枪射出充实水柱长度m
Hh水枪建筑物层高m
α:水枪射流倾角般45°60°
(2) 消火栓口需水压:
HxhHq+hd (12)
式中 Hxh:消火栓口水压kPa(mH2O)
hd:水流通水龙带压头损失kPa(mH2O)
Hq (13)
式中 Hm:充实水柱高度
αf:实验系数αf119+80(001Hm)4见表12
φ :水枪喷口直径df关系数器值见表13
表12 αf系数值表
HmmH2O
6
8
10
12
16
αf
119
119
120
121
124
表13 φ系数值表
dfmm
13
16
19
φ
00165
00124
00097
(3)水枪喷口设流量
qxh (14)
式中 qxh:水枪碰头射流量Ls
B:水流特性系数水枪喷口直径关见表14
Hq:水枪喷口造成某充实水柱需压力mH2O
表14 特性系数B
水枪喷口直径mm
13
16
19
22
B
0346
0793
1577
2836
(4)消防水龙带水头损失
(15)
式中 :水带程水头损失mH2O
Ld:水带长度m
Az:水带阻力系数见表15
表15 水带阻力系数Az值
水带材料
水带直径mm
50
65
80
麻织
001501
000430
000150
衬胶
000677
000172
000075
(5)道流量径
(16)
(17)
式中 Q:道设计流量m3s
D:道径m
v:道中水流速度ms
(6)程水头损失
(18)
式中 :段程水头损失kPa(mH2O)
L:计算段长度m
I:道单位长度水头损失kPam
v<12ms时:
v≥12ms时:
式中 :道计算径m
(7)局部水头损失
般情况室水道中局部阻力损失进行详细计算宜列水网程水头损失百分数算:
1)生产水网生活消防水网生产生活消防水网20
2)消火栓系统消防水网10
3)生产消防水网15
4)动喷水灭火系统网20
(8)水泵扬程
HbHq+hd+h+Hz (19)
式中 Hb:消防水泵扬程mH2O
Hz:消防水池低水面利消火栓间高差m
h:水头损失mH2O
(9)水箱设置高度
HHq+hd+h (110)
式中 H:水箱利点消火栓间高差mH2O
5 火灾危险等级划分
设置动喷水灭火系统场划分四等级请危险级中危险级严重危险级仓库危险级中中危险级严重危险级分ⅠⅡ级仓库危险级分ⅠⅡⅢ级
6动喷水灭火系统基设计参数
表17 民建筑工业厂房系统设计基参数
火灾危险等级
净空高度m
喷水强度(min1·m2)
作面积m2
轻危险级
≤8
4
160
中危险级
Ⅰ级
6
Ⅱ级
8
严重危险级
Ⅰ级
12
260
Ⅱ级
16
7动喷水灭火系统水利计算
(1)喷头流量
(111)
式中 q喷头流量Ls
K喷头流量特定系数见表19
P喷头工作压力KPakgcm2mH2O
表19 喷头流量特性系数值
p计量单位
KPa
mH2O
Kgcm2
K值
0133
0420
1330
(2)流量特性系数计算法
系统设计设计流量应利点处作面积碰头时喷水总量计算:
(112)
式中 Qs:系统设计流量Ls
qi:利点作面积喷头节点流量Lmin
n:利点作面积喷头数
(3)作面积计算法
1)系统设计流量计算:
(113)
2)系统理计算流量:
(114)
3)系统设计流量简化计算:
(115)
式中 :系统理计算流量Ls
W:设计喷水强度L(min·m2)
F:作面积m
2 消火栓水系统
21 方案拟定
1 消火栓水系统
消火栓水系统根水压分高压消防水系统时高压消防水系统低压消防水系统
(1) 高压消防水系统该系统需消防车移动式水泵加压直接消火栓接出水带水枪灭火根实践验效扑救火灾保证消防员安全生活生产消防水量时时水枪布置保护范围建筑物高处时水枪充实水柱应10m
(2) 时高压消防水系统该消防网时压力高泵站设置高压消防水泵发生火灾立刻启动消防水泵时加压网压力达高压消防水系统压力求
低压消防水系统该系统网时压力较低火车灭火时水枪水枪需压力消防车移动式消防泵产生低压消防水系统网压力应保证灭火时利点消火栓处水压001MPa
2 消火栓水系统水方式
(1) 室外水网直接供水室外水网供水量水压时候均满足室消火栓水系统需水量水压时优先选种方式进水应设置道倒流防器防回流污染生活饮水
(2) 水箱供种方式适室外水网日渐压力变化较水量满足室消防生活生产水种方式网应独立设置水箱生产生活合生活生产水动消防10min贮存备水量
(3) 水泵水箱水种方式适室外水网水压满足室消火栓水系统需水压保证消火栓灭火时足够消防水量设置水箱贮备10min室消防水量水箱补水采生活水泵严禁消防泵补水防消防时消防泵出水进入水箱水箱进入消防网出水应设单阀
(4) 分区水系统消火栓水系统中消火栓口静水压力应1MPa1MPa时应采取分区水系统分区水系统中低区水箱高度应保证低区利消火栓灭火时水枪充实水柱长度
(5) 区域集中消防水建筑区幢建筑组成建筑群设置1套消防水系统系统消防供水量幢计算系统压力标高高幢建筑计算高位水箱设置高幢建筑屋顶高处区域幢建筑发生火灾时效控制
根消防规范知该建筑高层标高24m高层建筑接合建筑参数相关规范分析较该厂房消火栓水系统设计方案拟定:时高压消防水系统消防水水箱室外蓄水池水泵接合器供水系统分区
22 消火栓水系统布置
1室消火栓布置道布置
(1)保证安全供水室消防水道应布置成环状室消防立少2根时少两根立相连组成环状网
(2)阀门设置位置应便网检修太影响供水原阀门数量n1
(3)消火栓布置般应保证层相邻2消火栓射出充实水柱时达室部位高度H≤24m体积V≤5000m3库房采支充实水柱达室点水枪
(4)消火栓应设置走道楼梯等附等明显易取点般间距25m
(5)室消火栓安装高度应距11m栓出口方宜墙壁垂直便操作水头损失较屋顶应设检查消火栓
2消防泵房布置
(1)水泵基础面尺寸水泵机座尺寸边水泵机座宽出100~150mm水泵基础顶面高出面100~300mm
(2)水泵机组基础端间基础端墙面距离般10m泵房行通道12m
(3)台水泵宜设置独立吸水组水泵少设2根吸水应设置少2根出水消火栓水环网连接
(4)消防水泵广泛采离心水泵根水泵轴线方离心水泵分卧式泵立式泵2种水泵出水量应计算消防水量水泵杨程满足消防水量情况保证系统利点消防设备需水压组消防水泵般采备两备台水泵般采联组合备水泵工作力应台消防工作水泵
3水泵接合器布置
(1)超4层厂房库房设消防立住宅超五层公建筑高层民建筑工业建筑室应设消防水泵接合器
(2)水泵接合器端室消火栓水网底层引致室外端进口供消防车移动水泵加压室网供水
(3)水泵接合器墙壁式3种水泵接合器接口双接口接口直径65mm80mm2种室网连接直径应100mm设阀门止回阀安全阀
(4)水泵接合器应设室外便消防车接供水点时考虑周围15~40m功供消防车取水室外消火栓蓄水池
(5)水泵接合器间距宜20m
(6)水泵接合器数量应室消防水量水泵接合器流量计算确定水泵接合器流量10~15Ls
23 材设备连接
工程属低层厂房 建筑消防设计规范关规定楼应设置室外消火栓系统喷淋储水量加压设备
1消火栓消火栓采普通单栓消火栓箱成品消火栓箱铝合金边框茶色玻璃门面单栓装DN65麻织水带条 长25M喷枪根口径19MM
2消火栓系统阀门均应常开铅封链条锁住 明显启闭标志室阀门采夹式蝶阀室外采明杆闸阀阀门工作压力采PN10
3建筑物消火栓采外热镀锌钢
4DN<100mm时采丝扣连接DN≥100mm时采卡箍连接
5室外埋采球墨铸铁胶圈连接
6消火栓系统道安装完毕应试压 试验压力系统压力15倍 试验压力100MPa
7道防腐明装镀锌钢接口处外壁刷红丹防锈漆两道整根道外壁刷面漆两道
24 消火栓水系统设计计算
1利消火栓出口压力计算
根高层建筑消火栓水系统求:厂房消防水量10Ls需2股射流股射流量qxh≥5Ls水枪射出充实水柱长度Hm≥10m采直径65mmL25m麻织水袋水枪喷口直径初步选19mm根公式12计算消火栓口水压:
HHq+hd
根设计规范Hm10m时αf120水枪喷口直径19mm时φ00097
Hq()mH2O1358mH2O
hdAzLdq2xh000430×25×25269mH2O
消火栓口水压:
HHq+hd1358+2691627mH2O
校核水枪设流量查表14 B1577
qxh46Ls<5Ls
:述计算效应提高充实水柱长度选Hm12m理求:
Hq()mH2O169mH2O
hdAzLdq2xh000430×25×52229mH2O
时消火栓口水压:
HHq+hd169+29198mH2O
校核水枪射流量:
Qxh516Ls>5Ls
:消火栓水系统利消火栓出口水压198mH2O
2消火栓间距
高层民建筑设计防火规范求消火栓间距应保证层部位两消火栓水枪充实水柱时达
(1)水龙带效长度:Ld08×2520m
(2)水枪充实水柱水面投影长度:LsHmsin45°12×849m
(3)消火栓保护半径:RfLd+Ls20+8492849m
(4)消火栓布置间距:L2818m
消火栓布置间距应28m泵房水箱间应设消火栓厂房四层层设4消火栓
3消火栓水道计算
(1)考虑2股水柱时作1中计算知支水枪流量52Ls根消防立实际流量104Ls
(2)根消防设计规范知消火栓水道流速般1418ms宜25ms流速V14ms时
径 D009797mm
消火栓立径选100mm
径D100mm时
v4QᴫD213ms<25ms
取消防立径DN100
(3)考虑建筑物发生火灾时环状网保证2根立消防水消防水量Q2×104208Lsv14ms时
径 D0137m137mm>125mm
消火栓环状网径选125mm
D125mm时
v4QᴫD217ms<25ms
取消火栓环状网径DN125
4计算利路水头损失
图21示段12345678910该系统利路水利计算程见表21
表21 利路水利计算表
节点
段
流量(L·s1)
长m
径mm
流速(m·s1)
iKPam
hyKPa
hjKPa
hKPa
1
1~2
52
42
100
066
009
0378
00378
042
2
2~3
104
131
100
132
037
4847
04847
533
3
3~4
104
164
125
085
012
1968
01968
216
4
4~5
156
711
125
127
026
18486
18486
2033
5
5~6
156
48
125
127
026
1248
01248
137
6
6~7
156
05
125
127
026
013
0013
014
7
7~8
156
18
125
127
026
0468
00468
051
∑h3026KPa309mH2O
图21 消火栓水系统计算草图
5 消防水泵扬程计算
根公式19计算消防水泵扬程:
HbHq+hd+h+Hz
169+29+309+162
3909mH2O
该建筑物室消防水量208Ls消火栓需压力3909mH2O选择两台水泵流量20Ls扬程40mH2O消防水泵备
6水箱高度容积计算
1)水箱容积
VfQt104×10×60624m3
Q<25Ls水箱应设12m3
2)水箱高度
公式110计算水箱高度:
HHq+hd+h169+29+3092289m
3 动碰水灭火系统
31 方案拟定
动喷水灭火系统种火灾发生时动喷水灭火时发出火警信号灭火系统种灭火系统具高灵敏度灭火成功率扑灭建筑初期火灾非常效灭火设备动喷水灭火系统碰头开闭式连接分闭式喷水灭火系统开式喷水灭火系统闭式喷水灭火系统分湿式动喷水灭火系统干式动喷水灭火系统干湿式动喷水灭火系统预作动喷水灭火系统等
1 湿式动喷水灭火系统
湿式喷水灭火系统闭式喷头道系统湿式报警阀报警装置供水设施等组成该系统报警阀前道始终充满压力水称湿式喷水灭火系统湿系统火灾发生时高温气流高温火焰闭式喷头热敏感元件炸裂脱落喷水灭火时网中水静止变流动水流指示器感应送出电信号报警控制器指标某某区域持续喷水造成湿式报警阀部水压低部水压原处关闭状态发片动开启时压力水通湿式报警阀流干配水时进入延迟器继压力开关动作水利警铃发出火警信号外压力开关直接连锁动启动消防水泵根水流指示器压力开关信号控制器动启动消防水泵网加压供水达持续动喷水灭火目始终充满水系统网会受环境温度限制该系统适室温度4~70℃建筑物构筑物
2 干式动喷水灭火系统
干式喷水灭火系统湿式喷水灭火系统相似报警阀结构作原理系统般闭式喷头道系统充气设备干式报警阀报警装置供水设备等组成碰头应采直立型碰头安装采干式垂型喷头干式动喷水系统适室温度低4℃高70℃建筑物构筑物官网容积宜超1500L设排气装置时宜超3000L
3 干湿式动喷水灭火系统
干湿式喷水灭火系统般闭式喷头道系统充气双重作阀报警装置供水设备等组成种系统具湿式干式喷水灭火系统性安装冬季采暖期长建筑物寒冷季节干式系统温暖季节湿式系统系统形式基干式系统相区报警阀采干湿式报警阀
4 预作动喷水灭火系统
预作喷水灭火系统般闭式喷头道系统预作阀报警装置供水设备探测器控制系统等组成预作系统预作阀道中时补充水充压缩空气氮气空闭式喷头火灾探测器时布置保护区域发生火灾时探测器动作发出火警信号报警器核实信号误发出动作指令开预作阀开启排气阀网充水命网充水时间应超3min着火势继续扩闭式喷头热敏原件融化炸裂喷头动喷水灭火系统中控制根道水压降低动开启消防泵进行灭火该系统早期发现火灾报警动喷水灭火性安装性高道迅速充水应道末端设排气阀门灭火时排道积水应设排水阀门适时允许水渍损害高级重建筑物干式灭火系统适场
次设计厂房位吉林省长春市冬季采暖时间长接合分析次设计方案拟定湿式动喷水灭火系统
32 动喷水灭火系统布置
1 碰头布置
(1)直立型垂型喷头布置包括根配水支喷头间距相邻配水支间距应根系统喷水强度喷头流量系数工作压力确定表31规定24m
表31 根配水支喷头间距相邻配水支间距
喷水强度(L•min1•m2)
正方形布置边长m
矩形行四边形布置长边边长m
1喷头保护面积m2
喷头端墙距离m
4
44
45
200
22
6
36
40
125
18
8
34
36
115
17
≥12
30
36
90
15
(2) 吊顶型喷头吊顶安装喷头外直立型垂型标准喷头溅水盘顶板距离应75mm应150mm
(3) 净空高度800mm闷顶技术夹层燃物时应设喷头
(4) 喷头粱通风排桥架等障碍物间水距离竖距离应符合动喷水灭火系统设计规范(GB50084)相关求
(5) 喷头间水距离喷头墙面距离喷头保护面积见表11喷头布置形式长方形
(6) 宽度超80cm矩形风道直径超1m圆形风道面应设置喷头
2 报警阀组布置
动喷水灭火系统应设报警阀组报警阀组般包括报警阀控制阀试警铃阀放水阀水力警铃压力开关报警阀前压力表等(湿式系统延迟器)保护室钢屋架等建筑构件闭式系统应设独立报警阀组
报警阀组控制碰头数应符合列规定:
①湿式系统预作系统宜超800干式系统宜超500
②配水支时安装保护吊顶方方空间喷头时数量较侧喷头计入报警阀组控制喷头总数
③串联接入湿式系统配水干动喷水灭火系统应分设置独立报警阀组控制喷头数计入湿式阀组控制喷头总数
④报警阀组控制高低位置喷头高程差宜50m
⑤报警阀组距面高度宜12m
3道系统设置
动喷水灭火系统应消火栓水系统分开设置困难时合消防水泵报警阀前必须分开设置报警阀官道应设置水设施配水工作压力12MPa
(1)动喷水灭火系统网1报警阀控制道系统1单元网报警阀道分立配水干配水配水支
(2)报警阀组控制利防火分区高 楼层配水支末端设置末端试水装置防火分区楼层利点喷头处仅安装DN25试水阀
(3)立高处设动排气阀充气系统高层配水高处设动排气阀
(4)配水网立基准配水俩侧根配水支控制标准碰头数轻危险级中危险级场超8时吊顶安装喷头配水支侧喷头数均超8严重危险级仓库危险级场喷头数均超6
(5)水安装道应坡度坡立充水道坡度00002标准工作状态允许道坡度00004
(6)轻危险级中危险级场配水支配水控制标准碰头数应超表32规定
表32 轻危险级中危险级场中配水支配水控制标准喷头数
公称径mm
控制标准喷头数
轻危险级
中危险级
25
1
1
32
3
3
40
5
4
50
10
8
65
18
12
80
48
32
100
64
(7) 短立末端试水装置连接径应25mm
33 材安装
1 配水道采外壁热度锌
2 系统道连接采法兰连接报警阀前采壁防腐钢时焊接连接
3 系统中直径100mm道分段采法兰连接件连接水段法兰间道长度15m立法兰间距跨度2楼层净空高度8m场立均设法兰
4 道支架吊顶距离表示
33 道支架吊顶间距表
公称直径mm
25
32
40
50
80
100
距离m
35
40
45
50
60
65
34 动喷水灭火系统设计计算
1 基设计参数
(1)中危险Ⅰ级
(2)设计喷水强度:W6L(min·m2)
(3)计算作面积:F160m2
(4)利喷头工作压力:p98000Pa仅水箱供水时利喷头工作压力pmin5×98000Pa
(5)动喷水灭火系统持续喷水时间1h
2根楼层面图喷头矩形布置长边间距L133m短边间距L232m配水网布置L133m作配水支间距边缘支距墙093m支中喷头间距32m末端喷头距墙093m配水两侧碰头距配水均16m喷头配水网布置见图31图32
3作面积法作系统计算
(1)作面积尺寸确定
厂房第四层利点处划定作面积作面积矩形边长:
L1212×1518m
式中 L矩形作面积长边m
F面积建筑F160m2
矩形作面积短边长BFL160÷15181054m
(2)利点处作面积范围
作面积高层利点处长边行配水支短边垂直配水支图41中虚线范围作面积作面积4根配水支根支4喷头作面积16喷头实际作面积:
FLB1248×12131514m2
(3)系统水力计算
作面积计算规利碰头1开始逐段计算流量水头损失逐点计算工作压力作面积段流量增加利碰头1工作压力10mH2O计算程见表41示
表41 作面积法水力计算表
段
公称直径mm
Q(L·s1)
Q2
A(s2·L2)
Lm
hmH2O
流速(m·s1)
1~2
25
133
177
04367
32
247
271
2~3
32
266
708
009386
32
212
331
3~4
32
399
1592
009386
32
478
496
4~5
40
532
2830
004453
16
202
424
5~6
50
532
2830
001108
33
102
271
6~7
80
1064
11321
000127
35
050
212
7~8
80
1596
25041
000127
31
099
318
8~18
100
2128
45284
000027
42
514
271
18~22
100
2128
45284
000027
251
307
271
∑h2211
图31 动喷水灭火系统面计算示意图
系统设计流量:Qs2128Ls
节点22处压力H22式计算:
H22H0+12∑h+HKP+HSL+Z
(10+12×2211+4+2+197)mH2O
62232mH2O
意4喷头围合范围均碰水强度Wp设计喷水强度较:
WpL(min·m2)756L(min·m2)>600 L(min·m2)
较结果合格
4水箱高度计算
火灾初期消防水泵启动前高位水箱供水时采作面积利4喷头12ab时喷水计算流量水压利点喷头1工作压力5mH2O计算程见表42示
表42 特性系数法水箱高度水力计算表
节点
段
KB
节点压力PimH2O
流量
(L·s1)
Q2(L2·s2)
公称径mm
道阻A(s2·L2)
节点间距m
量长度m
计算长Lm
水头损失hmH2O
标高差m
节点qi
段Q
1
K042
5
094
1~2
094
088
25
04367
32
06
38
146
2
K042
646
107
2~3
201
404
32
009386
32
20
52
197
3
K042
843
107
3~4
201
404
32
009386
32
0
32
121
4
K042
964
107
4~5
201
404
40
004453
16
03
19
034
5
K042
998
107
5~6
201
404
50
001108
33
18
51
023
6
B1002
1021
107
6~7
402
1616
80
000127
35
08
43
009
7
B1002
1030
107
7~8
402
1616
80
000127
33
0
33
007
8
B1002
1037
107
8~22
402
1616
100
000027
671
53
724
032
197
22
B1002
3040
107
22~24
402
1616
100
000027
65
135
785
034
∑h603
图32 动喷水灭火系统计算草图
表42中知道程损失局部损失∑h603mH2O∑h´计算:
∑h´(603+005+005)mH2O613mH2O
水箱高度:HH0+∑h´+Z(5+613+167)mH2O2783mH2O
水箱容积:V2128×60×1012768m3
消防水箱供水系统利喷头低工作压力外必须校核喷水强度否符合规范求取12ab四喷头作均喷水强度核算系统利喷头1工作压力5mH2O计算述四喷头流量分wq1094Lsq2107Lsqa094Lsqb107
Ls均喷水强度Wp计算:
Wp
L(min·m2)
589L(min·m2)
动喷水灭火系统设计规范(GB 50048)规定轻中危险级均喷水强度低设计喷水强度85系统中危险Ⅰ级设计设计喷水强度6L(min·m2)均喷水强度Wp设计设计喷水强度85较
589L(min·m2)>6L(min·m2)×085510L(min·m2)
较结果合格屋顶水箱果置2785m标高位置满足求建筑物屋顶标高1680m2785m必须设置消防增压设备
参考文献
[1]李天荣龙莉莉陈金华建筑消防设备工程重庆:重庆学出版社20105
[2]建筑设计防火规范GB5004595[S]中国计划出版社(2005年版)
[3]高层民建筑设计防火规范GB50016-2006[S]中国计划出版社
[4]动喷水灭火设计规范GB500842001[S]中国计划出版社(2005年版)
[5]全国通水排水标准图集S1S2S3中国建筑标准设计研究(2002)